In this paper, we report investigations into temperature and flow field inside a recessed space outside a high-rise residential building in Hong Kong. The investigated 30-story recessed spaces contain 30 air-conditioners, and one or two horizontal plates. We studied the worst-case scenario in summer when all air-conditioner units reject condenser heat into this space. The predictions by using FLUENT 5.0, a computational fluid dynamics code, show that presence of one plate inside the space would cause the overall excess temperature at condenser entrance to fall up to 30%. The presence of two plates would make this figure to be around 40%.
机译:在本文中,我们报告了对香港一栋高层住宅建筑外的凹进空间内温度和流场的调查。被调查的30层隐蔽空间包含30台空调和一个或两个水平板。我们研究了夏季所有空调机将冷凝器热量排入该空间的最坏情况。通过使用FLUENT 5.0(一种计算流体动力学代码)进行的预测表明,空间内一块板的存在会导致冷凝器入口处的总体过高温度下降30%。两个板块的存在将使该数字约为40%。