Seasonal variations of indoor air quality and thermal conditions and their correlations in 220 classrooms in the Midwestern United States

机译:室内空气质量和热条件的季节变化及其在美国中西部220教室中的相关性

获取原文
获取原文并翻译 | 示例

摘要

In this 2-year, seasonally-repeated study, the research team surveyed the baseline conditions of indoor air quality (IAQ) and thermal conditions (TC) of 220 classrooms in the Midwestern region (Nebraska and Iowa) of the United States of America. Seasonal variations of each IAQ and TC variable and correlations between variables were also examined. CO2 concentrations were acquired from each of the classrooms while simultaneously monitoring outdoor CO2 concentration, particle counts, formaldehyde concentration, air temperature, globe temperature, and relative humidity. Ventilation rate and absolute humidity level were also estimated. The results showed the mean CO2 concentration of 220 classrooms during the occupied hours throughout the measured seasons was 1171 ppm. The average ventilation rate was 5.6 L/s-person, below the suggested value by ASHRAE Std 62.1. Other IAQ and TC variables were found to be well-maintained when compared to the NIOSH or EPA standards. Large seasonal variations were found in humidity level, ventilation rate, particle counts, and formaldehyde concentration. It is therefore suggested that the monitoring of classroom IAQ and TC should be done periodically across the whole school year to comprehensively describe the conditions. There were significant correlations between IAQ and TC variables, which suggest relationships between these variables. This study revealed the baseline conditions and examined the seasonal variations of the classroom IAQ and TC of the region for the first time. Further benefits, such as improvement of classroom IAQ and TC, may result from this study.
机译:在这2年的季节性重复研究中,研究团队调查了美国中西部地区(内布拉斯加州和爱荷华州)的220课堂室内空气质量(IAQ)和热情(TC)的基线条件。还检查了每个IAQ和TC变量和变量之间的相关性的季节变化。从每个教室中获得CO 2浓度,同时监测室外CO 2浓度,颗粒计数,甲醛浓度,空气温度,环状温度和相对湿度。还估计通风率和绝对湿度水平。结果表明,在整个测量的季节占用时间内220个教室的平均CO2浓度为1171ppm。 Ashrae STD 62.1的建议价值低于5.6万人,平均通风率为5.6立方米。与Niosh或EPA标准相比,发现其他IAQ和TC变量是良好的维护。在湿度水平,通风率,颗粒计数和甲醛浓度下发现了大的季节变异。因此,建议监测课堂IAQ和TC应在整个学年期间定期进行,以全面描述条件。 IAQ和TC变量之间存在显着的相关性,这表明这些变量之间的关系。本研究揭示了基线状况,并首次审查了该地区教室IAQ和TC的季节变化。本研究可能导致课堂IAQ和TC等进一步的益处,例如课堂IAQ和TC。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号