首页> 外文期刊>IEEE Transactions on Applied Superconductivity >Study on recovery time of a superconducting fault current limiterwith adjustable trigger current level
【24h】

Study on recovery time of a superconducting fault current limiterwith adjustable trigger current level

机译:可调触发电流水平的超导故障限流器恢复时间的研究

获取原文
获取原文并翻译 | 示例

摘要

The recovery time of a transformer type SCFCL (superconducting fault current limiter) with adjustable trigger current level, is studied experimentally The recovery time is defined as the required time of zero current period of SCFCL for recovery from its current limiting mode to its waiting mode. A trial SCFCL, which was designed and made, is tested to measure the recovery time with various fault time. The experimental results show that the recovery time depends on the fault time. When the fault time is longer than 200 ms, the recovery time becomes shorter and approaches a certain value (a few ten ms) as the fault time is longer
机译:实验研究了具有可调触发电流电平的SCFCL型超导故障限流器的恢复时间。恢复时间定义为SCFCL从零电流模式恢复到等待模式所需的零电流周期的时间。经过设计和制造的SCFCL试用版经过测试,可以测量各种故障时间下的恢复时间。实验结果表明,恢复时间取决于故障时间。故障时间大于200 ms时,故障时间越长,恢复时间越短,接近某个值(几十毫秒)。