A trial three-phase SCFCL with adjustable trigger current level was proposed and fabricated. Current limiting characteristics of the SCFCL with parallel and series connection using two of the three-phase SCFCLs was investigated experimentally in a model power system consisting a small synchronous generator and an artificial parallel transmission lines. The pair of the SCFCL was installed in one of three phases of the fault line. The fault current limiting characteristics of the pair of SCFCL at one line grounded (1 LG) fault was studied with various fault phases. In every test case, the SCFCL limited the fault current below a certain level. In the series-connection cases, which one or both of the pair of SCFCLs turn into the current limiting mode can be controlled by calibrating the trigger current level of each SCFCL. It was observed that it depends on the fault phase. In the parallel connection cases, both of the pair of SCFCLs turn into current limiting mode nearly simultaneously in every fault phase.
机译:提出并制造了具有可调触发电流水平的试验三相SCFCL。在一个由小型同步发电机和人工并联传输线组成的模型电力系统中,通过实验研究了使用两个三相SCFCL进行并联和串联连接的SCFCL的限流特性。这对SCFCL安装在故障线的三相之一。研究了不同故障阶段下一对SCFCL在一条接地线(1 LG)故障时的故障限流特性。在每个测试案例中,SCFCL都会将故障电流限制在一定水平以下。在串联连接的情况下,可以通过校准每个SCFCL的触发电流电平来控制一对SCFCL中的一个或两个变成限流模式。据观察,这取决于故障阶段。在并行连接的情况下,在每个故障阶段,这对SCFCL几乎都同时进入限流模式。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号