首页> 外文期刊>IEEE Transactions on Applied Superconductivity >Repetitive operation of three-phase superconducting fault current limiter in a model power system
【24h】

Repetitive operation of three-phase superconducting fault current limiter in a model power system

机译:模型电力系统中三相超导故障限流器的重复操作

获取原文
获取原文并翻译 | 示例

摘要

Superconducting fault current limiters (SCFCLs) are expected to improve reliability and stability of power systems. To introduce an SCFCL to power systems, the repetitive operation at the severe continuous faults is one of the important function. The recovery time of the proposed 3-phase FCL was confirmed experimentally to be sufficiently short for the repetitive operation. This paper shows the experimental results and discussion on the repetitive current limiting operation of the 3-phase SCFCL, which was demonstrated in a model power system. The test condition was that the fault line is open at the fault within 100 ms and is re-closed within 930 ms, but the fault is not cleared during the interval while the fault line is open. It was confirmed that the SCFCL started to limit the fault current immediate after the fault and recover to the stand-by mode during the interval, and limited the fault current again at the re-closure without any degradation of the trigger current level and the limiting impedance.
机译:超导故障电流限制器(SCFCL)有望提高电力系统的可靠性和稳定性。为了将SCFCL引入电力系统,在严重的连续故障下重复运行是一项重要功能。实验证明,所提出的三相FCL的恢复时间对于重复操作而言足够短。本文显示了在模型电源系统中演示的三相SCFCL的重复限流操作的实验结果和讨论。测试条件是故障线在100毫秒内在故障处断开,并在930毫秒内重新闭合,但是在故障线断开期间的间隔内无法清除故障。可以确认,SCFCL在故障发生后立即开始限制故障电流,并在该时间间隔内恢复到待机模式,并在重新闭合时再次限制故障电流,而不会降低触发电流水平和限制阻抗。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号