首页> 外文期刊>IEEE Transactions on Applied Superconductivity >Current limiting characteristics of transformer type superconducting fault current limiter
【24h】

Current limiting characteristics of transformer type superconducting fault current limiter

机译:变压器式超导故障限流器的限流特性

获取原文
获取原文并翻译 | 示例

摘要

The transformer type superconducting fault current limiter is composed of a series transformer and a superconducting current limiting device. The primary winding of the transformer is connected in series to the power transmission line, and the secondary winding is short-circuited through the superconducting current limiting device whose normal resistance plays an important role in limiting the fault current. According to our previous investigations, the basic characteristics and the design indexes of the transformer type superconducting fault current limiter were clarified. In this paper, the results of the current limiting test of a 5 kVA class transformer type superconducting current limiter are analyzed in detail, and the limiting characteristics such as the dependency of the initiation current of the limiting operation on the fault phase angle are shown.
机译:变压器式超导故障限流器由串联变压器和超导限流装置组成。变压器的初级绕组串联到输电线路,次级绕组通过超导电流限制装置短路,该装置的法向电阻在限制故障电流中起着重要作用。根据我们先前的研究,阐明了变压器型超导故障限流器的基本特性和设计指标。本文详细分析了5 kVA级变压器型超导电流限制器的电流限制测试结果,并显示了限制特性,例如限制操作的启动电流对故障相角的依赖性。