首页> 外文期刊>Applied Superconductivity, IEEE Transactions on >Test of Maximum Endurable Quenching Voltage of YBCO-Coated Conductors for Resistive Superconducting Fault Current Limiter
【24h】

Test of Maximum Endurable Quenching Voltage of YBCO-Coated Conductors for Resistive Superconducting Fault Current Limiter

机译:电阻超导故障电流限制器的YBCO涂层导体的最大耐久淬火电压测试

获取原文
获取原文并翻译 | 示例

摘要

Voltage tolerance during quench is one of the most important parameters for YBCO-coated conductors, especially for resistive type superconducting fault current limiter (SFCL) applications. How much voltage can be sustained per unit length of YBCO tape when experiencing fault current indicates the total required amount of the tapes to construct a resistive SFCL. In this paper, a step-down transformer is used to provide the short-current. As the voltage of the secondary side is not continuously variable, we change the voltage per unit length of the YBCO tape by varying the length of the tape. And the effect of the duration of short-current is also considered. A series of test have been performed to determine the maximum voltage drop that each YBCO tape can stand at fault current. The V-t curve has been measured after the tape experiencing successive quenches. Through a large number of experiments we will acquire the maximum endurable quenching voltage per unit length of YBCO tapes when experiencing short-current for different durations. The results presented in this paper would provide useful information for optimizing the design of a resistive SFCL.
机译:淬火期间的电压容限是YBCO涂层导体最重要的参数之一,尤其是对于电阻型超导故障限流器(SFCL)应用而言。遇到故障电流时,每单位长度的YBCO胶带可以承受多少电压,这表明构造电阻式SFCL所需的胶带总量。在本文中,使用降压变压器来提供短路电流。由于次级侧的电压不是连续可变的,因此我们通过改变胶带的长度来更改YBCO胶带每单位长度的电压。并且还考虑了短电流持续时间的影响。已经进行了一系列测试,以确定每个YBCO胶带在故障电流下可以承受的最大电压降。在胶带经历连续的淬火之后,已经测量了V-t曲线。通过大量的实验,当在不同的持续时间内经历短电流时,我们将获得YBCO胶带每单位长度的最大耐久淬火电压。本文介绍的结果将为优化电阻式SFCL的设计提供有用的信息。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号