To explore the impact on the efficiency of water mist with compound additives for extinguishing polystyrene foam fire, this paper has carried out the experimental research on water mist with NaCl+SDBS com⁃pound additives for extinguishing polystyrene foam fire. With SDBS of different concentration being added into 2.5%NaCl solution, the temperature acquisition system is used to measure temperature. With the temperature and the time of fire extinguishing as characteristic parameter, fire-extinguishing time is compared. The results show that: the efficiency of extinguishing fire was markedly improved and fire-extinguishing time changed from 500 seconds when the only additive of NaCl was contained to 190 seconds when NaCl+0.4%SDBS was contained.%为探究含复合添加剂的细水雾对灭聚苯乙烯火效率的影响,本文开展了含氯化钠+十二烷基苯磺酸钠复合添加剂的细水雾对灭聚苯乙烯火的实验研究。在2.5%氯化钠溶液中加入不同浓度的十二烷基苯磺酸钠,利用温度采集系统测量火场温度,以火场温度与灭火时间为表征参数,将其灭火时间进行对比。结果表明:含复合添加剂的细水雾对灭聚苯乙烯火效率有了明显提高,灭火时间由单一氯化钠添加剂时的500秒变为含有氯化钠和0.4%SDBS时的190秒。