首页> 外文会议>Water Environment Federation 75th annual technical exhibition amp; conference (WEFTEC 2002) >APPLICATION OF CHLORAMINES FOR REUSE WATER DISINFECTION AT THE CITY OF LAS VEGAS WATER POLLUTION CONTROL FACILITY
【24h】

APPLICATION OF CHLORAMINES FOR REUSE WATER DISINFECTION AT THE CITY OF LAS VEGAS WATER POLLUTION CONTROL FACILITY

机译:氯胺在拉斯维加斯市水污染控制设施的回用水消毒中的应用

获取原文
获取原文并翻译 | 示例

摘要

This study evaluates the application of chloramines to disinfect the reuse effluentrnproduced by the City of Las Vegas Water Pollution Control Facility (WPCF) to irrigaterngolf courses. Although the current chlorination process consistently meets the totalrncoliform standard, it results in high costs associated with chemical consumption.rnLaboratory and field tests were performed using filtered effluent from the WPCF. Testsrnincluded chlorine demand determination, chloramination tests, and disinfection tests.rnThe chlorine demand of the treated wastewater was found to be 3.0 mg/L. Bestrnmonochloramine formation was accomplished when a 3.5:1 chlorine-to-ammonia ratiornwas applied. A 4:1 chlorine-to-ammonia ratio (ammonia dosage of 1.0 mg/L) resulted inrn100% removal of total coliform. A cost estimate indicated that the chloraminationrnprocess would result in a 48% reduction in the current chemical cost.
机译:这项研究评估了使用氯胺消毒由拉斯维加斯市水污染控制设施(WPCF)产生的回用废水到irrigaterngolf课程的情况。尽管当前的氯化过程始终符合总大肠菌群标准,但导致化学药品消耗高昂的成本。实验室和现场测试是使用WPCF过滤后的废水进行的。测试包括对氯的需求量测定,加氯测试和消毒测试。对处理后的废水的氯需求量为3.0 mg / L。当使用氯与氨的比例为3.5:1时,形成最佳的一氯胺。氯与氨之比为4:1(氨剂量为1.0 mg / L)导致大肠菌群的去除率达到100%。成本估算表明,氯胺化工艺将使目前的化学成本降低48%。