首页> 外文会议>Signal processing, pattern recognition, and applications ; Computer graphics and imaging >A PHASOR ESTIMATION METHOD FOR THE TRANSIENT SIGNALS IN A POWER SYSTEM WITH A WIND FARM
【24h】

A PHASOR ESTIMATION METHOD FOR THE TRANSIENT SIGNALS IN A POWER SYSTEM WITH A WIND FARM

机译:带有风电场的电力系统暂态信号的相量估计方法

获取原文
获取原文并翻译 | 示例

摘要

This paper proposes a modified dynamic phasor estimation method to calculate the phasor of a fundamental frequency component with time-variant amplitude. The two exponential functions of the decaying dc offset and the fundamental frequency component are replaced by Taylor series and the LSE (Least Square Error) technique is used to estimate the amplitudes and the time constants of the decaying components. The performance of the proposed algorithm is evaluated by using computer-simulated signals based on simple equations and fault current signals generated by using DFIG wind generator models in MATLAB Simulink. The test results indicate that the proposed algorithm can accurately estimate the decaying amplitude and the time constant of the fundamental frequency component.
机译:提出了一种改进的动态相量估计方法,用于计算具有时变幅度的基频分量的相量。衰减的直流偏移和基频分量的两个指数函数被泰勒级数取代,并且使用LSE(最小二乘误差)技术来估计衰减分量的幅度和时间常数。通过基于简单方程的计算机模拟信号和使用MATLAB Simulink中的DFIG风力发电机模型生成的故障电流信号,可以评估所提出算法的性能。测试结果表明,该算法可以准确估计出基频分量的衰减幅度和时间常数。