首页> 外文会议>IEEE PES Asia-Pacific Power and Energy Engineering Conference >The protection strategy analysis of the last circuit breaker in the 1 + 1/2 operation mode
【24h】

The protection strategy analysis of the last circuit breaker in the 1 + 1/2 operation mode

机译:1 + 1/2操作模式下最后一个断路器的保护策略分析

获取原文

摘要

This paper makes a brief introduction to the protection logic of the last circuit breaker of arrester type. Afterwards, two novel protection strategies for the last circuit breaker of arrester type are proposed aiming at solving the problem that the protection of the arrester type last circuit breaker at the inverter side of the high-end converter cannot function properly when it's out of operation. Based on the simulation model of the ±800 kV Yunnan-Guangdong UHV AC-DC hybrid systems, a simulation verification is carried out on the PSCAD / EMTDC platform, and the result indicates the correctness of the proposed two novel protection strategies for the arrester type last circuit breaker.
机译:本文简要介绍了避雷器型最后一个断路器的保护逻辑。 之后,提出了两个用于最后一个断路器的新型保护策略,旨在解决在高端转换器的逆变器侧的避雷器型最后一个断路器的保护时无法正常运行的问题。 基于±800 kV云南 - 广东UHV AC-DC混合系统的仿真模型,在PSCAD / EMTDC平台上进行了模拟验证,结果表明了提出的避雷器类型的两种新型保护策略的正确性 最后一个断路器。