首页> 外文会议>International Electronics Symposium on Engineering Technology and Applications >Cascaded PID Temperature Controller for FOPDT Model of Shell-and-Tube Heat Exchanger Based on Matlab/Simulink
【24h】

Cascaded PID Temperature Controller for FOPDT Model of Shell-and-Tube Heat Exchanger Based on Matlab/Simulink

机译:基于MATLAB / SIMULINK的壳管热交换器FOPDT模型级联PID温度控制器

获取原文

摘要

Cascade control is one of the most successful methods for improving single loop control performance. This control can stabilize the system, minimalize both of oscillation and integral error of interference in manipulation variables. Cascade control structure consists of two controllers where loop feedback in the loop feedback. This research takes a case on original shell-and-tube heat exchanger and simulated using Matlab/Simulink. Cascade control is used to stabilize outlet temperature even there is interference. Shell-and-tube heat exchanger is modeled using first order plus delay time (FOPDT). The type of controller is used PID standard with Ziegler-Nichols tuning method. Performance of cascade control is tested by providing inlet fluid flow disturbance. The experiment got the best performance on PI control (secondary controller) with parameter of Kp and Ti worth 1.375 and 2. PI control produces smallest IAE amount 34.57. Test control of cascade (primary controller) obtained a result that control of PID produces the best response. PID control with parameter values Kp, Ti, and Td of 2.85, 53.06 and 13.265 gave the smallest IAE of 601.54 and the fastest rise time of 121.5 seconds. From this research, it is concluded that the shell-and-tube heat exchanger system can use cascade control to regulate the temperature stably even with an unstable fluid flow.
机译:级联控制是提高单环控制性能的最成功的方法之一。该控件可以稳定系统,最小化了操纵变量干扰的振荡和积分误差。级联控制结构由两个控制器组成,其中环路反馈中的环路反馈。本研究采用原始壳管热交换器和使用Matlab / Simulink模拟的情况。即使存在干扰,级联控制用于稳定出口温度。壳管热交换器使用一阶加延迟时间(FOPDT)进行建模。使用Ziegler-Nichols调谐方法使用PID标准的控制器类型。通过提供入口流体流动扰动来测试级联控制的性能。该实验在PI控制(二级控制器)上获得了最佳性能,其中KP和TI的参数值1.375和2. PI控制产生最小的IAE金额34.57。级联(主控制器)的测试控制获得了PID控制PID产生最佳响应的结果。使用参数值Kp,Ti和Td的PID控制为2.85,53.06和13.265给出了601.54的最小IAE,最快的上升时间为121.5秒。从本研究开始,壳牌热交换器系统可以使用级联控制,即使具有不稳定的流体流动,稳定地调节温度。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号