首页> 外文会议>International Electrical and Energy Conference >Defect Analysis and Preventive Measures of Main Transformer Bushing Based on Frequency Domain Dielectric Spectroscopy
【24h】

Defect Analysis and Preventive Measures of Main Transformer Bushing Based on Frequency Domain Dielectric Spectroscopy

机译:基于频域介电光谱的主变压器衬套的缺陷分析及预防措施

获取原文

摘要

The health status of main transformer bushing is directly related to the safe and stable operation of power grid. This paper introduces an abnormal dielectric loss factor of glass fiber reinforced plastic dry bushing of 220 kV main transformer. Firstly, the casing defects were determined based on the frequency domain dielectric spectrum. Then, the causes of the casing defects were analyzed by the partial discharge test, the casing disintegration inspection, the final screen dielectric loss test and the electromagnetic field simulation calculation. Finally, the diagnosis method and the preventive measures of the glass fiber reinforced dry casing defects were proposed. The research results of this paper have certain reference and guiding significance for the safe operation of this type of main transformer bushing.
机译:主变压器衬套的健康状况与动力电网的安全稳定运行直接相关。 本文介绍了220 kV主变压器的玻璃纤维增强塑料干衬套的异常介电损耗因子。 首先,基于频域介电谱确定壳体缺陷。 然后,通过局部放电测试,壳体崩解检查,最终筛网介电损耗测试和电磁场模拟计算分析壳体缺陷的原因。 最后,提出了诊断方法和玻璃纤维增强干燥套管缺陷的预防措施。 本文的研究结果对于这种类型的主变压器衬套的安全操作具有一定的参考和指导意义。