Analysis on the influencing factors of faults at the remote end impacting the UHV interconnected power grid

机译:影响UHV互联电网的远端故障影响因素分析

获取原文

摘要

After the Central China grid getting connected with the North China grid through the UHVAC demonstration project, a new phenomenon is discovered according to some simulations. That is, the faults at the remote end of the UHV interconnected grid results in significant power fluctuation and voltage drop on the UHV transmission line and even system splitting. But the faults near the UHV line only have marginal effects. In this paper, the detail was introduced, and a three-generator equivalent system was built to analyse this phenomenon. The results show that both angle difference and the rotational inertia of the generators have effect on it. This paper also indicates that modifying the mode of operation or the unit commitment is helpful to improve the system stability.
机译:在中国中央电网与华北电网联系到UHVAC示范项目后,根据一些模拟发现了一种新的现象。也就是说,UHV互连网格的远程端处的故障导致UHV传输线甚至系统分割的显着功率波动和电压降。但UHV线附近的故障只具有边缘效应。在本文中,介绍了细节,建立了三个发电机等效系统以分析这种现象。结果表明,发电机的角度差和旋转惯性都对其产生了影响。本文还表示修改操作模式或单位承诺有助于提高系统稳定性。