首页> 外文会议>International conference on frontiers of energy and environment engineering >Analysis of optimum U-tube diameter in ground source heat pump
【24h】

Analysis of optimum U-tube diameter in ground source heat pump

机译:地源热泵中最佳U形管直径分析

获取原文

摘要

In order to reduce the pump energy consumption in GSHP,pipe diameter is increased to solve the problem.When flux of pump is constant,by choosing pipes of different diameters for numerical calculation and simulation,the pump energy consumption and the heat transfer of ground heat exchanger are both analyzed.It could be concluded that an appropriate increase of pipe diameter could reduce pump energy consumption and enhance heat transfer.However,when the pipe diameter is too large,the hot short circuit of ground heat exchanger would be serious,thus,increase of pipe diameter should be based on the hot short circuit between branch pipes.It is given in the paper that the suggest pipe diameter would exist during 30 mm to 40 mm.The analysis would reduce energy consumption of pump,improve a guarantee for the selection of pipe diameter and the design of GSHP with great guide and economic benefits.
机译:为了减少GSHP中的泵能量消耗,增加管道以解决问题。泵的通量是恒定的,通过选择不同直径的管道,用于数值计算和仿真,泵能量消耗和地热传递的热传递交换器都分析。可以得出结论,管道直径的适当增加可以降低泵能量消耗并增强热转印。然而,当管道直径过大时,地面热交换器的热短路将是严重的,因此管道直径的增加应基于分支管道之间的热短路。本文给出的是,建议管道直径在30mm至40mm期间。分析将减少泵的能耗,提高泵的能耗,提高了泵的能耗。具有极大指南和经济效益的管道直径和GSHP设计的选择。