This paper presents a modelling study on the evaluation of the passive cooling strategies for Pei Min sport complex at Miri. The squash centre has experienced excessively high temperature during peak hours that results in complains from the users. We discussed several passive cooling mechanisms and proposed four strategies for the sport centre. Thermal energy simulations were performed on these strategies using OpenStudio to evaluate their impact on the hourly temperature profile within the building. It was found that the peak temperature during the noon was significantly reduced when conductive material was applied at the lower surface of the roof, and the top of the roof was coated with white paint. However, insulating the roof also leads to weaker heat dispersion from the building which lower the rate of temperature drop in the late afternoon. Partitioning the roof was found to have similar effect as insulating roof. Air infiltration is essential for promoting air movement and regulating the temperature within the building. It was found the complex already have sufficient opening for the full effect of air infiltration.
机译:本文介绍了Miri的Pei Min Sport Complex的被动冷却策略评估的建模研究。壁球中心在高峰时段经历了高温,导致用户抱怨。我们讨论了几种被动冷却机制,提出了体育中心的四种策略。使用OpenStudio对这些策略进行热能模拟,以评估其对建筑物内的每小时温度曲线的影响。发现在屋顶的下表面施加导电材料时,中午期间的峰值温度显着降低,并且屋顶的顶部涂有白色涂料。然而,绝缘屋顶也导致较弱的建筑物较弱,从而降低了下午晚期的温度下降速率。发现屋顶被发现与绝缘屋顶类似的效果。空气渗透对于促进空气运动并调节建筑物内的温度至关重要。它发现复杂已经有足够的开口,用于充分效应空气渗透。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号