Impacts of energy retrofits on ventilation rates, CO2-levels and occupants' satisfaction with indoor air quality

机译:能量改造对通风率,二氧化碳水平和占用者对室内空气质量的影响

获取原文

摘要

INSULAtE-project assessed impacts of energy retrofits on indoor environmental quality and occupants' satisfaction. Most common retrofit actions included changing new windows and installing heat recovery into exhaust ventilation system. This paper presents results related to ventilation in Finnish apartment buildings before and after the retrofits. Average ventilation rates (from exhaust vents) in buildings with mechanical ventilation were 0.43 ACH before and 0.48 ACH after the retrofits. Average CO2 concentrations were 750 ppm before and 715 ppm after the retrofits, correspondingly. Percentage of occupants satisfied with IAQ was 22% before and 41% after the retrofits. In conclusion, ventilation rates, CO2-levels, and occupants' satisfaction with IAQ were improved in most retrofitted buildings.
机译:绝缘项目评估了能源改造对室内环境质量和占用者的满意度。最常见的改造行动包括更换新窗口并将热量恢复安装到排气通风系统中。本文介绍了在改造前后芬兰公寓楼的通风相关结果。机械通风的建筑物中的平均通风率(来自排气通风口)为0.43Ach,在改造后和0.48 ACH。平均二氧化碳浓度为750ppm之前,结束后715ppm,相应地。 IAQ满足于IAQ的占用者的百分比为22%,结转后41%。总之,在大多数改装建筑物中,通风率,二氧化碳水平和占用者对IAQ的满意度得到了改善。