首页> 外文会议>International Conference on Energy and Environmental Research >Effects of pressure loss coefficients of heat exchanger on thermal performance of the dry cooling tower
【24h】

Effects of pressure loss coefficients of heat exchanger on thermal performance of the dry cooling tower

机译:热交换器压力损失系数对干冷却塔热性能的影响

获取原文

摘要

Crosswind deteriorates thermal performance of the natural draft dry cooling tower (NDDCT) mainly due to the unfavorable pressure distribution at tower entrance. Thus, effects of air cooled heat exchanger with various pressure loss coefficients are investigated with numerical simulation. The vortex inside the tower would cut down air inflow of heat exchanger of sideward and leeward parts. A quite large exponent of pressure loss coefficient expression of heat exchanger contributes to reduce heat transfer unevenness among cooling deltas, and would generate a small enhancement for the overall thermal performance of the tower.
机译:Crosswind由于塔入口处的不利压力分布而劣化天然干燥冷却塔的热性能。 因此,利用数值模拟研究了空气冷却热交换器具有各种压力损失系数的影响。 塔内的涡流将减少侧向和背风部件的热交换器空气流入。 热交换器的压力损失系数表达的相当大的指数有助于降低冷却趋扩化之间的热传递不均匀性,并且会对塔的整体热性能产生小的增强。