首页> 外文会议>ECCE 2013 >Parameter Design and Impacts on Power Quality of a Q-f Droop Curve Based Islanding Detection Method
【24h】

Parameter Design and Impacts on Power Quality of a Q-f Droop Curve Based Islanding Detection Method

机译:参数设计与对基于Q-F下垂曲线电能质量的影响

获取原文

摘要

An islanding detection method for grid-connected inverter based on the reactive power versus frequency ( Q-f) characteristic of the distributed generation (DG) and the islanded load is considered in this paper. With proper reactive power perturbation proportional to the deviation of the frequency based on the Q-f droop curve, the DG is able to lose its stable operation and detect the moment of islanding once an islanding condition occurs. Meanwhile, the added reactive power would lower the power factor and degrade power quality. In this paper, parameter design is investigated and the impacts of the method on the power quality are revealed. The studies are performed and verified by simulations in a multi-inverter system in the MATLAB/Simulink environment.
机译:本文考虑了基于分布发电(DG)的无功功率与频率(Q-F)和孤岛负载的基于电网连接逆变器的孤岛检测方法。通过基于Q-F下垂曲线的频率的偏差成比例的适当的无功功率扰动,DG能够失去其稳定的操作并检测一旦岛状状态发生岛的岛屿。同时,增加的无功功率将降低功率因数,降低电力质量。在本文中,研究了参数设计,并揭示了该方法对电力质量的影响。通过在Matlab / Simulink环境中的多变频器系统中进行模拟进行和验证研究。