首页> 外文会议>2013 IEEE Energy Conversion Congress amp; Exposition >Parameter design and impacts on power quality of a Q-f droop curve based islanding detection method
【24h】

Parameter design and impacts on power quality of a Q-f droop curve based islanding detection method

机译:基于Q-f下垂曲线的孤岛检测方法的参数设计及其对电能质量的影响

获取原文
获取原文并翻译 | 示例

摘要

An islanding detection method for grid-connected inverter based on the reactive power versus frequency (Q-f) characteristic of the distributed generation (DG) and the islanded load is considered in this paper. With proper reactive power perturbation proportional to the deviation of the frequency based on the Q-f droop curve, the DG is able to lose its stable operation and detect the moment of islanding once an islanding condition occurs. Meanwhile, the added reactive power would lower the power factor and degrade power quality. In this paper, parameter design is investigated and the impacts of the method on the power quality are revealed. The studies are performed and verified by simulations in a multi-inverter system in the MATLAB/Simulink environment.
机译:本文考虑了一种基于分布式发电(DG)和孤岛负载的无功与频率(Q-f)特性的并网逆变器孤岛检测方法。通过基于Q-f下降曲线的适当无功功率扰动与频率偏差成正比,一旦出现孤岛情况,DG便会失去稳定的运行并检测到孤岛的力矩。同时,增加的无功功率会降低功率因数并降低电能质量。本文对参数设计进行了研究,揭示了该方法对电能质量的影响。这些研究是通过在MATLAB / Simulink环境中的多逆变器系统中进行仿真来执行和验证的。