Open cycle desiccant-cooling system (DCS), which is operated by using exhaust heat energy below 373K, has been known as one of the most important non-freon non-electric cooling technologies. Its operating condition has been discussed by using computer simulation and widely improved co-efficiency of the system and operating conditions1,2). Although water spraying and evaporating system of DCS were used for cooling, the size and co-efficiency of DCS system has not been improved sufficiently. We proposed and studied experimentally a new type of Humidity Swing Air-conditioning system (HSA) which consists of desorption cooling system in the adsorbate instead of cooling system by water spraying. Cooling temperature 10 K is obtained and reduction of regeneration heat energy by desorption cooling brings COP=1.03. These results indicated that the proposed HSA could be operated as a high efficiency cooling system.
机译:开放循环干燥剂冷却系统(DCS),通过使用低于373K的废热能量操作,已被称为最重要的非氟利昂非电气冷却技术之一。通过使用计算机仿真和广泛提高了系统的共同效率和操作条件1,2),已经讨论了其操作条件。尽管DCS的喷水和蒸发系统用于冷却,但DCS系统的尺寸和共效尚未得到充分提高。我们提出并研究了一种新型湿度摆动空调系统(HSA),该空调系统(HSA)由吸附剂中的解吸冷却系统组成,而不是喷水的冷却系统。通过解吸冷却获得冷却温度10k并通过解吸冷却降低再生热能,带来COP = 1.03。这些结果表明,所提出的HSA可以作为高效冷却系统操作。