首页> 美国卫生研究院文献>Elsevier Public Health Emergency Collection >Site verification and modeling of desiccant-based system as an alternative to conventional air-conditioning systems for wet markets
【2h】

Site verification and modeling of desiccant-based system as an alternative to conventional air-conditioning systems for wet markets

机译:基于现场的干燥剂系统验证和建模可替代传统的湿市场空调系统

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Desiccant cooling system for active humidity control and to conserve energy has been in commercial applications for over two decades. However, its use in humid wet markets has never been examined. A gas-fired desiccant cooling system has been installed in a wet market in Hong Kong. In this study, the annual energy saving in conjunction with the use of desiccant cooling system was investigated by in-situ measurements, site surveys and simulations. The verified computer model was used for further simulations. It was found that for the use of a minimum ventilation rate of 10.3 L/s/person, the use of desiccant cooling system as compared to conventional system saved 4% of the energy and could achieve the desired space conditions. A parametric study under various ventilation rates indicated that use of desiccant cooling system in wet markets in hot and humid Hong Kong would lead to energy and energy cost savings, as well as CO emission reduction amounting from 1% to 13%. The savings were more evident when wet markets were designed for a ventilation rate of 20 L/s/person. Furthermore, the actual occupancy profile, and lighting and small power densities determined in this study would be useful for future studies on wet market.
机译:用于主动湿度控制和节能的干燥剂冷却系统已经在商业应用中使用了二十多年。但是,从未在潮湿的潮湿市场中使用过它。香港的一个潮湿市场已安装了燃气干燥剂冷却系统。在这项研究中,通过现场测量,现场调查和模拟研究了结合使用干燥剂冷却系统的年度节能效果。经过验证的计算机模型用于进一步的仿真。结果发现,对于最低通风速率为10.3 L / s /人的使用,与传统系统相比,使用干燥剂冷却系统可节省4%的能量,并可以达到所需的空间条件。在各种通风率下进行的一项参数研究表明,在炎热潮湿的香港湿市场上使用干燥剂冷却系统将节省能源和能源成本,并将CO排放量减少1%至13%。当湿市场设计为通风量为20 L / s /人时,节省的效果更加明显。此外,本研究确定的实际占用情况以及照明和小功率密度对于将来在湿市场上的研究将是有用的。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号