首页> 外文会议>Conference on Interdisciplinary Problems in Environmental Protection and Engineering >Analysis of operating conditions of a cooling installation with carbon dioxide
【24h】

Analysis of operating conditions of a cooling installation with carbon dioxide

机译:用二氧化碳冷却装置的操作条件分析

获取原文

摘要

In response to international regulations, natural refrigerants such as carbon dioxide are more and more frequently used in the refrigeration industry. Due to thermodynamic properties, R-744 is used in the transcritical cycle as an individual refrigerant. In the hereby article, high pressure of CO2 and air temperature values were analysed. The measurements were conducted on the gas cooler side and involved external air temperature values in the summer period between 1 June to 30 September 2018. The "Booster" installation was used in one of Polish supermarkets. Correlations required to determine the optimal pressure of carbon dioxide depending on ambient temperature were presented in the article. The equations presented hereby allowed to maximize the energy efficiency ratio. An optimal high pressure for one of the correlations from literature was calculated on the basis of the measurement of ambient temperature. Actual and optimal pressure values of carbon dioxide were compared in the analysed period of time.
机译:为了应对国际法规,在制冷工业中越来越多地使用二氧化碳等天然制冷剂。由于热力学性质,R-744用于跨临界循环作为单独的制冷剂。在此,分析了CO 2和空气温度值的高压。测量在气体冷却器侧进行,并在2018年6月1日至30日夏季期间涉及外部空气温度值。“助推器”安装用于波兰超市之一。在制品中提出了根据环境温度确定二氧化碳最佳压力所需的相关性。特此允许的方程允许最大化能量效率。基于环境温度的测量计算来自文献的一个相关性的最佳高压。在分析的时间段内比较了二氧化碳的实际和最佳压力值。