首页> 外文期刊>E3S Web of Conferences >Analysis of operating conditions of a cooling installation with carbon dioxide
【24h】

Analysis of operating conditions of a cooling installation with carbon dioxide

机译:用二氧化碳分析制冷设备的运行条件

获取原文
   

获取外文期刊封面封底 >>

       

摘要

In response to international regulations, natural refrigerantssuch as carbon dioxide are more and more frequently used in the refrigeration industry. Due to thermodynamic properties, R-744 is used in the transcritical cycle as an individual refrigerant. In the hereby article, high pressure of CO2 and air temperature values were analysed. The measurements were conducted on the gas cooler side and involved external air temperature values in the summer period between 1 June to 30 September 2018. The “Booster” installation was used in one of Polish supermarkets. Correlations required to determine the optimal pressure of carbon dioxide depending on ambient temperature were presented in the article. The equations presented hereby allowed to maximize the energy efficiency ratio. An optimal high pressure for one of the correlations from literature was calculated on the basis of the measurement of ambient temperature. Actual and optimal pressure values of carbon dioxide were compared in the analysed period of time.
机译:根据国际法规,诸如制冷剂之类的天然制冷剂在制冷工业中越来越多地被使用。由于具有热力学特性,R-744在跨临界循环中用作单独的制冷剂。在本文中,分析了二氧化碳的高压和空气温度值。测量是在气体冷却器侧进行的,涉及的外部空气温度值是在2018年6月1日至9月30日的夏季。在波兰一家超市中使用了“ Booster”装置。该文章介绍了根据环境温度确定最佳二氧化碳压力所需的相关性。由此提出的等式允许最大化能量效率比。根据环境温度的测量结果,计算出其中一种相关关系的最佳高压。在分析的时间段内比较了二氧化碳的实际压力值和最佳压力值。