HEAT TRANSFER ENHANCEMENT BY TWISTED TAPE INSERTS DURING CONDENSATION OF R-245fa INSIDE A HORIZONTAL TUBE

机译:在水平管内的R-245Fa冷凝期间,通过扭曲胶带插入胶带刀片增强

获取原文

摘要

An experimental investigation has been made to study the enhancement of heat transfer coefficient during condensation of the pure vapor of R-245fa inside a horizontal tube by inserting twisted tap of different twist ratio in the range of 4.3 to 6.4. For each inserted tube and the plain tube, the data were acquired for mass fluxes in the range of 100 kg/m~2·s to 200 kg/m~2·s for the entire range of vapor quality from 0.1 to 0.9. The twisted tape is more effective at the low mass flux and in low vapor quality region as compared to high vapor quality region. The highest enhancement of heat transfer is 25 percent above the plain flow for the twist ratio of 4.3 at refrigerant mass flux of 100 kg/m~2·s.
机译:已经进行了一种实验研究,研究了通过在4.3至6.4的范围内插入水平管内的R-245Fa内部的纯蒸汽凝结过程中的传热系数的增强。对于每个插入的管和普通管,对于100kg / m〜2·s至200kg / m〜2·s的全部蒸汽质量范围为0.1至0.9,可以获得数据的质量通量。与高蒸气质量区域相比,双绞带在低质量磁通量和低蒸汽质量区域中更有效。热传递的最高增强是在100kg / m〜2·s的制冷剂质量通量下的捻度为4.3的平原流量的25%。