首页> 外文会议>National Fluid Mechanics and Fluid Power Conference >NUMERICAL STUDY ON HEAT TRANSFER AND PRESSURE DROP CHARACTERISTICS OF A TUBE EQUIPPED WITH WIRE COIL INSERT
【24h】

NUMERICAL STUDY ON HEAT TRANSFER AND PRESSURE DROP CHARACTERISTICS OF A TUBE EQUIPPED WITH WIRE COIL INSERT

机译:线圈插入管配备管的传热和压降特性的数值研究

获取原文

摘要

Present work reports CFD studies of Nusselt number, friction factor and overall enhancement efficiency for a tube fitted with wire coil. The result showed that the wire coil with p/d of 0.434, 0.651 and 0.868 can enhance heat transfer up to 4.98, 5 and 4.3 times respectively and friction factors up to 5.82, 4.06 and 3.3 times respectively, in comparison with plain tube. Wire coil inserts with e/d of 0.038, 0.128 and 0.171 provide heat transfer enhancement around 4.99, 5.92 and 7.6 times respectively and friction factor enhancement up to 5.82, 19.97 and 35.7 times respectively than plain pipe.
机译:目前的工作报告了对线圈配合管的管道数,摩擦因子和整体增强效率的CFD研究。结果表明,与平原管相比,含有0.434,0.651和0.868的线圈,0.434,0.651和0.868分别可以分别增强高达4.98,5和4.3次,摩擦因子高达5.82,4.06和3.3次。带有E / D的线圈插入件为0.038,0.128和0.171,可分别为4.99,5.92和7.6次的传热增强,摩擦系数增强程度可分别比平原管道的5.82,19.97和35.7次。