首页> 外文会议>International Conference on Indoor Air Quality and Climate >INDICATORS OF MOISTURE AND VENTILATION SYSTEM CONTAMINATION IN U.S. OFFICE BUILDINGS AS RISK FACTORS FOR RESPIRATORY AND MUCOUS MEMBRANE SYMPTOMS: ANALYSES OF THE EPA BASE DATA
【24h】

INDICATORS OF MOISTURE AND VENTILATION SYSTEM CONTAMINATION IN U.S. OFFICE BUILDINGS AS RISK FACTORS FOR RESPIRATORY AND MUCOUS MEMBRANE SYMPTOMS: ANALYSES OF THE EPA BASE DATA

机译:美国水分和通风系统污染指标作为呼吸系统症状的危险因素:EPA基础数据分析

获取原文

摘要

Many studies have associated moisture or mold in residences with respiratory symptoms, but few studies have been conducted in office buildings. We assessed associations between moisture and ventilation system contamination and lower respiratory and mucous membrane symptoms in the U.S. EPA BASE data from 100 U.S. office buildings, using multivariate regression models. One set of models showed lower respiratory symptoms almost tripled with lack of cleaning of drip pans under air-conditioning cooling coils (odds ratio (95% confidence interval) = 2.8 (1.2-6.5). Other models associated lack of cleaning of either drip pans or cooling coils, and water damage in mechanical rooms, with increased mucous membrane symptoms. Some moisture-related risks found by other studies were not replicated here. Overall, findings suggest that moisture or contamination in ventilation systems or occupied spaces in office buildings may have adverse health effects. Studies with more rigorous measurement of environmental factors and health outcomes are necessary.
机译:许多研究在呼吸道症状的居住中有相关的水分或霉菌,但在办公楼中进行了很少的研究。我们评估的水分和通风系统污染和下呼吸道和粘膜症状之间的关联,从100个美国写字楼美国EPA的基础数据,利用多元回归模型。一组模型显示出低呼吸道症状几乎增加了两倍,随着空调冷却盘管缺乏清洁滴水盘(差距比(95%置信区间)= 2.8(1.2-6.5)。其他模型缺乏清洁滴水平底锅或者冷却线圈,以及机械房中的水损坏,粘膜症状增加。此处没有复制其他研究发现的一些水分相关的风险。总体而言,调查结果表明,通风系统中的水分或污染的办公楼中的空间可能存在不良健康效果。需要更严格测量环境因素和健康结果的研究。

著录项