INDICATORS OF MOISTURE AND VENTILATION SYSTEM CONTAMINATION IN U.S. OFFICE BUILDINGS AS RISK FACTORS FOR RESPIRATORY AND MUCOUS MEMBRANE SYMPTOMS: ANALYSES OF THE EPA BASE DATA

机译:呼吸和粘膜症状的风险因素:美国办公大楼中水分和通风系统污染的指标:EPA基础数据分析

获取原文

摘要

Many studies have associated moisture or mold in residences with respiratory symptoms, but few studies have been conducted in office buildings. We assessed associations between moisture and ventilation system contamination and lower respiratory and mucous membrane symptoms in the U.S. EPA BASE data from 100 U.S.office buildings, using multivariate regression models. One set of models showed lower respiratory symptoms almost tripled with lack of cleaning of drip pans under air-conditioning cooling coils (odds ratio (95% confidence interval) = 2.8 (1.2-6.5). Other models associated lack of cleaning of either drip pans or cooling coils, and water damage in mechanical rooms, with increased mucous membrane symptoms. Some moisture-related risks found by other studies were not replicated here. Overall, findings suggest that moisture or contamination in ventilation systems or occupied spaces in office buildings may have adverse health effects. Studies with more rigorous measurement of environmental factors and health outcomes are necessary.
机译:许多研究将住宅中的湿气或霉菌与呼吸道症状相关联,但在办公大楼中进行的研究很少。我们使用多元回归模型评估了美国100所办公楼的美国EPA BASE数据中的水分和通风系统污染与下呼吸道和粘膜症状之间的关联。一组模型显示下呼吸道症状几乎翻了三倍,而在空调冷却盘管下缺乏清洁滴油盘(几率(95%置信区间)= 2.8(1.2-6.5)。或冷却盘管,机械室中的水损害以及粘膜症状加剧。其他研究发现的与湿气有关的风险未在此处重复进行。总体而言,研究结果表明通风系统或办公楼占用空间中的湿气或污染可能具有对健康的不利影响:有必要对环境因素和健康结果进行更严格的测量。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号