Impact of directly-connected generator design on balanced fault behavior

机译:直接发生的发电机设计对平衡故障行为的影响

获取原文

摘要

This paper considers the impact that the design of a directly connected generator will have upon the behaviour of an entire power system under the influence of a balanced three-phase bolted (LLLG) fault. Initially a method for illustrating the effect of the connection of a single generator upon the entire network is demonstrated. This is utilized to derive algebraic comparisons between the fault currents, voltage disturbances and the generator fault in-feeds that are produced in a power system in which an existing generator and GSU (generator step-up) transformer is replaced by a directly connected generator. The qualitative relationships are verified with data obtained from simulation of a 17-bus test system and a 600-bus realistic power transmission network. The results highlight that the variation in design of a single generator may produce perceptible change to network fault behaviour in an appreciable portion of a power system.
机译:本文考虑了直接连接发生器的设计将在平衡三相螺栓(LLLG)故障的影响下的整个电力系统的行为的影响。最初,演示了一种用于说明在整个网络上的单个发生器的连接的效果的方法。这用于导出在现有发生器和GSU(发电机升压)变压器的电力系统中产生的故障电流,电压干扰和发电机故障进料之间的代数比较,其中由直接连接的发生器代替。使用从17总线测试系统的模拟和600总线现实电力传输网络获得的数据验证了定性关系。结果突出显示单个发电机的设计的变化可以在电力系统的可明显部分中产生对网络故障行为的可感知变化。