首页> 外文会议>International Symposium on High-voltage engineering >Failures in power system transformers and appropriate monitoring techniques
【24h】

Failures in power system transformers and appropriate monitoring techniques

机译:电力系统变压器的故障以及适当的监控技术

获取原文

摘要

Failure analysis of 188 power transformers in the voltage range of 88kV to 765kV and MVA rating from 20 to 800 is presented. The analysis of the data shows that in smaller transformers ageing related failures are dominant. In the medium MVA rating class, tap-changer failures constitute the highest failure rate. In the large transformers, insulation coordination failure is the most common cause in the early service life of the transformer. This study is an update of earlier investigations.Appropriate monitoring techniques have been suggested with a view to transformer size and voltage rating.
机译:提出了188个电源变压器的故障分析,电压范围为88kV至765kV和20至800的MVA等级。数据分析表明,在较小的变压器中,老化相关的失败是显性的。在介质MVA评级类中,抽头更换器故障构成最高故障率。在大型变压器中,绝缘配位故障是变压器早期使用寿命中最常见的原因。本研究是更新早期调查的。已经提出了对变压器大小和电压额定值的观点来提出的恰当的监测技术。