首页> 外文会议> >Failures in power system transformers and appropriate monitoring techniques
【24h】

Failures in power system transformers and appropriate monitoring techniques

机译:电力系统变压器故障和适当的监控技术

获取原文

摘要

Failure analysis of 188 power transformers in the voltage range of 88 kV to 765 kV and MVA rating from 20 to 800 is presented. The analysis of the data shows that in smaller transformers ageing related failures are dominant. In the medium MVA rating class, tap-changer failures constitute the highest failure rate. In the large transformers, insulation coordination failure is the most common cause in the early service life of the transformer. This study is an update of earlier investigations. Appropriate monitoring techniques have been suggested with a view to transformer size and voltage rating.
机译:提出了在88 kV至765 kV电压范围和20至800的MVA额定值范围内的188个电力变压器的故障分析。数据分析表明,在较小的变压器中,与老化相关的故障占主导地位。在中等MVA等级等级中,分接开关故障构成最高故障率。在大型变压器中,绝缘配合失效是变压器早期使用寿命中最常见的原因。这项研究是对早期研究的更新。考虑到变压器的尺寸和额定电压,已经提出了适当的监视技术。