A high performance liquid cooling architecture for high power processors in less than 45 mm height electronics chassis (1U rack space) was proposed and investigated experimentally. A review of several system cooling approaches from CPU to data center was also provided. The present proposed method employs conventional heat pipes to transport local CPU heat to the edge of an electronics module coupled with system liquid cold plates. As coolant from external cooling distribution unit in data center flows through the system cold plates in the rack, CPU heat load is rejected to data center cooling facility. Capable of removing the processor power as high as 450W is demonstrated from a prototype built. Experiments were conducted to characterize the prototype thermal performance between liquid inlet and heat pipe evaporator base. A 25 mm × 25 mm heat block was used to simulate CPU and provide heat source to the heat pipe evaporator base. The impacts of heat transfer rate, flow rate, and liquid inlet temperature were evaluated. The total thermal resistance of below 0.090°C/W was achieved at water flow rate of 11/min and heat transfer rate of 450W.
机译:提出了高功率处理器的高性能液体冷却架构,在小于45毫米的高度电子底盘(1U机架空间),并实验研究。还提供了对来自CPU到数据中心的几种系统冷却方法的审查。本提出的方法采用传统的热管来将局部CPU热量运送到与系统液体冷板联接的电子模块的边缘。由于来自数据中心的外部冷却分配单元的冷却剂流过机架中的系统冷板,CPU热负荷被拒绝到数据中心冷却设施。能够从构建的原型中展示高达450W的处理器电源。进行实验以表征液体入口与热管蒸发器基座之间的原型热性能。使用25mm×25mm的热块来模拟CPU并向热管蒸发器基座提供热源。评估了传热速率,流速和液体入口温度的影响。在0.090℃/ w以下的热阻在11 / min的水流速和450W的传热速率下实现的总热阻。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号