Design parametric study of a lateral configured diabatic straight capillary tube with R-134a

机译:用R-134A设计横向配置型颌骨直毛管的参数研究

获取原文

摘要

An experimental investigation was conducted to observe the effect of sub-cooling degree on themass flow rate of R-134a through a diabatic laterally configured straight capillary tube. The variationof mass flow rate of refrigerant through the capillary with the sub-cooling degree is observed to beindependent of capillary tube geometry and the inlet pressure. When the diameter of the capillarytube decreased from 1.52 mm to 1.27 mm, the mass flow rate through the capillary tube alsodecreased by 16 percent. Also The mass flow rate of refrigerant was observed to increase by 12 to17 percentage in all the tested capillary tubes with an increase of sub-cooling from 6°C to 9°C.
机译:进行了实验研究以观察次冷度对的影响R-134a通过β横向配置的直毛管的质量流量。变异观察到通过毛细管的制冷剂质量流速与子冷却度进行独立于毛细管几何形状和入口压力。当毛细血管的直径管从1.52毫米降至1.27 mm,通过毛细管的质量流量也减少了16%。也观察到制冷剂的质量流量增加12至在所有测试毛细管中的17个百分比,从6℃达到9℃的子冷却增加。