Assessment of remaining insulation life of high voltage inductionmotors

机译:评估高压感应器的剩余绝缘寿命马达

获取原文

摘要

Various insulation tests were performed on the aged polyester/micainsulation of 3-6 kV rating motors. About 100 machine samples have beenretrieved after 11-22 years service in the field and tested beforerewinding. The tests include measurements of insulation resistance,polarization index, dissipation factors, partial discharges, and ACbreakdown voltage. The insulation resistance and polarization index tendto decrease with operating time, while the dissipation factor tip-up andpartial discharges show no clear tendency. The breakdown voltage showsgradual decrease with operating time. A good correlation is foundbetween the remaining breakdown voltage and a new index log (Rd/Rw), where Rd andRw are the insulation resistances measured under dryand wet conditions, respectively. Using these test data and a modernsoftware tool, the authors have developed a prototype expert system fora diagnostic consultation
机译:对老化的聚酯/云母进行了各种绝缘测试 3-6 kV额定电动机的绝缘。大约有100个机器样本 在野外工作11-22年后取回并经过测试 倒带。测试包括绝缘电阻的测量, 极化指数,耗散因数,局部放电和交流电 击穿电压。绝缘电阻和极化指数趋于 随工作时间而减少,而耗散因数增加并 局部放电没有明显的趋势。击穿电压显示 随着工作时间逐渐减少。发现良好的相关性 在剩余击穿电压和新的指数对数之间( R d / R w ),其中 R d R w 是在干燥条件下测得的绝缘电阻 和潮湿条件。使用这些测试数据和现代 软件工具,作者已经开发了一个原型专家系统,用于 诊断咨询