首页> 外文期刊>Russian electrical engineering >Calculation and Experimental Assessment of the Voltages on the Longitudinal Insulation of the Windings of Station Service Voltage Transformers under Resonant Overvoltages
【24h】

Calculation and Experimental Assessment of the Voltages on the Longitudinal Insulation of the Windings of Station Service Voltage Transformers under Resonant Overvoltages

机译:谐振过电压下站维修电压变压器绕组纵向绝缘电压的计算与实验评估

获取原文
获取原文并翻译 | 示例
           

摘要

Abstract—Under high-frequency oscillations of grid voltage, resonant overvoltages may develop inside transformer windings if the frequencies of the grid voltage oscillations are close to the resonant frequencies of the transformer windings. For transformer equipment—in particular, station service voltage transformers, which, in virtue of the specifics of their operation, may be subjected to the action of high-frequency oscillatory voltages—to withstand internal resonance, it is necessary to assess potential impacts on the internal insulation of their windings under resonance as early as the design stage. The transformer models applied in practice for numerical simulation of high-frequency transients in the transformer windings do not allow accurate reproduction of resonant voltage rises, as they do not provide for rigorous consideration of the frequency dependence of the losses. Direct measurements of the winding voltages under resonance are an alternative to the calculations; however, in practice, such measurements are difficult to make and it is not always possible to measure voltages that affect the insulation in the parts of the windings of interest. In the article, the possibility of determining the impacts on the longitudinal insulation of the windings under resonance by supplementing the measured results with analytical solutions of equations of transients in the windings is studied. The approaches considered in this paper are applicable not only to the station service voltage transformers, but also to other types of the transformer equipment.
机译:摘要 - 在电网电压的高频振荡下,如果电网电压振荡的频率接近变压器绕组的谐振频率,则谐振过电压可能在变压器绕组内部开发。对于变压器设备 - 特别是,驻车站维修电压变压器,借助于其操作的具体情况,可以对高频振荡电压的动作进行,以承受内部共振,有必要评估对此的潜在影响随着设计阶段,在共振下绕组的内部绝缘。在实践中应用的变压器模型在变压器绕组中的高频瞬变的数值模拟不允许精确再现谐振电压升高,因为它们不提供对损耗频率依赖性的严格考虑。在共振下绕组电压的直接测量是计算的替代方案;然而,在实践中,难以制造这种测量,并且并不总是可以测量影响感兴趣绕组的部分中的绝缘的电压。在本文中,研究了通过补充测量结果与绕组中的瞬变方程的分析解的测量结果来确定对共振下绕组的纵向绝缘的影响。本文考虑的方法不仅适用于站服务电压变压器,而且适用于其他类型的变压器设备。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号