Historical lightning data could be use to evaluate certain transmission line in power system network. By using historical data from lightning detection system with combined Magnetic Direction Finder and Time of Arrival method, lightning data mapping for West Java province was presented in this paper. According to the lightning data mapping from total recorded event, the peak current of the lightning was mostly ranged within 10 kA to 15 kA with median peak current value up to 20 kA. Bogor and Bandung had relatively high lightning density among other area within West Java province. Evaluation of lightning exposure for 150 kV transmission line on Bogor and Bandung were presented to determine which segment of the transmission line should be set as priority during routine monitoring and maintenance. Transmission fault or reclose event analysis using recorded lightning data was presented as a recommendation for further maintenance on the tower part prior to fault or reclose event, e.g., insulation string, ground wire or tower grounding.
机译:历史闪电数据可用于评估电力系统网络中的某些传输线。通过采用带有组合磁方向查找器和到达时间的雷击检测系统的历史数据,本文提出了西爪哇省的雷击数据映射。根据从总记录事件的闪电数据映射,闪电的峰值电流主要在10ka至15ka内,中值峰值电流值高达20ka。 Bogor和Bandung在西爪哇省内的其他地区具有相对较高的雷电密度。提出了对150 kV传输线的雷电曝光的评估,以确定在常规监测和维护期间应将传输线的哪个段设定为优先级。使用记录的闪电数据的传输故障或重新卷曲事件分析作为在故障或重新卷曲事件之前在塔部件上进行进一步维护的推荐,例如,绝缘串,地线或塔接地。