首页> 外文会议>IEEE/PES Transmission and Distribution Conference and Exposition >Overcurrent Coordination Study of the Electrical System of PDVSA Sur, Barinas
【24h】

Overcurrent Coordination Study of the Electrical System of PDVSA Sur, Barinas

机译:PDVSA Sur,Barinas电气系统的过流协调研究

获取原文

摘要

In this paper part of the results of an overcurrent coordination study for the 34.5/13.8-kV system of PDVSA Sur, operational area of Barinas, Venezuela, are presented. After previous load flow and short-circuit calculations, the protective devices of each distribution circuit were analyzed to choose new pickup currents, time-current characteristic (TCC) curves, time dials, and instantaneous settings for the phase-fault and ground-fault protection functions. The new settings improved the times of response of the short-circuit protective devices, the coordination time intervals, and the selectivity and reliability of the system.
机译:在本文中,介绍了PDVSA SUR,Barinas,委内瑞拉的PDVSA SUR,委内瑞拉的运营区域的34.5 / 13.8-KV系统的过流协调研究结果。在先前的负载流和短路计算之后,分析了每个分配电路的保护装置,选择新的拾取电流,时间电流特性(TCC)曲线,时间拨号和接地故障保护的瞬时设置职能。新设置改进了短路保护装置,协调时间间隔和系统的选择性和可靠性的响应时间。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号