Influence of tie-line reactance on damping of inter-area oscillation mode

机译:联络线电抗对区域间振荡模式阻尼的影响

获取原文

摘要

The influence of tie-line reactance on damping of inter-area oscillation mode is studied. The phenomenon of the inter-area mode damping ratio decreasing when inter-connection is strengthened is proposed. Main interconnected grids in China are tested by calculating sensitivity of eigenvalue to tie-line reactance, including Chuanyu-Mid China Grids, Northeast-North Grids, North-Mid Grids and Fujian-East Grids. A two- area system is constructed for further investigation. The study shows there is no strict linear relationship between tie-line reactance and damping of inter-area oscillation mode. For a large-scale system, the power transferred of which is comparatively small, it is possible that damping of inter-area mode decreases as tie-line reactance decreases, which is opposite to the commonly accepted opinion. Although the phenomenon is comparatively rare, it should be carefully paid attention to considering its strong influence under some critical stage. These tests also demonstrate that reinforcement of the conection between two bulk power grids is an effective way to mitigate oscillations in systems.
机译:研究了联络线电抗对区域间振荡模式阻尼的影响。提出了加强互连时区域间模态阻尼比降低的现象。通过计算特征值对联络线电抗的敏感性来测试中国的主要互联电网,包括川渝中电网,东北电网,东北电网,闽东电网和闽东电网。构建了一个两区域系统以供进一步研究。研究表明,联络线电抗与区域间振荡模式的阻尼之间没有严格的线性关系。对于传输功率相对较小的大规模系统,区域间模式的阻尼可能会随着联络线电抗的降低而降低,这与普遍接受的观点相反。尽管这种现象比较少见,但在某些关键阶段应仔细考虑其强烈影响。这些测试还表明,加强两个大电网之间的连接是减轻系统振荡的有效方法。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号