A statistical relation between breakdown voltage and the parameters characterizing the predischarge state at a short vacuum gap is discussed. The three following parameters were chosen: a voltage which causes an emission current of a measurable value (equal to 10/sup -6/ A), an electron field emission current measured at a selected voltage value, and the electric field amplification factor determined from the Fowler-Nordheim equation. For all the investigated relations, a regression analysis was carried out and the coefficient of determination was evaluated. Plane electropolished electrodes made of Cu and special electrodes made of Cu-Cr sinter used in a vacuum interrupter were investigated. All the relations studied prove that the three parameters can be treated as criteria for evaluating the electroinsulating properties of a short vacuum gap.
机译:讨论了击穿电压和表征短真空间隙下预放电状态的参数之间的统计关系。选择以下三个参数:产生可测量值(等于10 / sup -6 / A)的发射电流的电压,在选定电压值下测得的电子场发射电流以及由下式确定的电场放大系数Fowler-Nordheim方程。对于所有调查的关系,都进行了回归分析并评估了确定系数。研究了在真空灭弧室中使用的由Cu制成的平面电抛光电极和由Cu-Cr烧结制成的特殊电极。所有研究的关系证明,这三个参数可以作为评估短真空间隙的电绝缘性能的标准。