首页> 外文会议>IEEE/IAS Industrial and Commercial Power Systems Technical Conference >Single-Phase Ferroresonance in an Ungrounded System Causing Surge Arresters Failure during the System Energization
【24h】

Single-Phase Ferroresonance in an Ungrounded System Causing Surge Arresters Failure during the System Energization

机译:不接地系统中的单相铁磁谐振在系统通电期间导致电涌放电器故障

获取原文

摘要

Ferroresonance often occurs in power systems during system switching actions, which can create overvoltages and pose great risks to the equipment safety. In this paper, a single-phase ferroresonance incident during a system energization is presented, which occurred at a single-phase station service transformer in an ungrounded system, causing surge arresters' failure. The incident is investigated through PSCAD simulations and analytical analysis. The relay field record is used to compare with the simulation results in order to validate the PSCAD simulation model. Several case studies are conducted using PSCAD simulations to evaluate various contributing factors to this ferroresonance incident. The root cause of the incident is found to be the lack of ground during energization in the system. Field practices are recommended to be implemented before the system energization to avoid such incidents, which were proved to be effective by successfully energizing the system in the field following these practices.
机译:电力系统在切换过程中经常发生铁磁谐振,产生过电压,给设备安全带来极大的风险。本文介绍了在系统通电过程中发生的单相铁磁谐振事件,该事件发生在不接地系统中的单相厂用变压器上,导致避雷器故障。该事件通过PSCAD模拟和分析进行调查。继电器现场记录用于与仿真结果进行比较,以验证PSCAD仿真模型。使用PSCAD模拟进行了几个案例研究,以评估导致该铁磁共振事件的各种因素。事故的根本原因是系统通电期间接地不足。建议在系统通电之前实施现场实践,以避免此类事件,通过按照这些实践在现场成功地给系统通电,证明此类事件是有效的。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号