Lightning Overvoltages in Electrical Power System of a Power Plant

机译:发电厂电力系统中的雷电过电压

获取原文

摘要

This paper analyzes lightning overvoltage spikes in an internal network of a large power plant. The cases considered are direct stroke to the phase conductor of the connected power transmission line and back flashover resulting from the lightning stroke to the transmission tower or shield wire. To investigate the transmitted overvoltages through transformers, high frequency models of the transformers are used. The voltage rise at the secondary side of each connected transformer at different voltage levels in the house load network of the power generation plant is analyzed. Protective measures are compared in order the study how to mitigate the transferred overvoltage at the different house load power system levels and to ensure that the impulse voltage is within the basic insulation level (BIL) of the connected equipment. Simulations using different combinations of protective surge arrestors and protective capacitors are done and recommendations on overvoltage protection are presented.
机译:本文分析了大型发电厂内部网络中的雷电过电压尖峰。所考虑的情况是直接向连接的输电线路的相线冲撞,以及由于雷击到输电塔或屏蔽线而导致的向后闪络。为了研究通过变压器传输的过电压,使用了变压器的高频模型。分析了发电厂的房屋负载网络中每个连接的变压器的次级侧在不同电压水平下的电压升高。比较保护措施是为了研究如何减轻在不同的房屋负载电力系统水平上传递的过电压,并确保脉冲电压在所连接设备的基本绝缘水平(BIL)范围内。使用保护性电涌放电器和保护性电容器的不同组合进行了仿真,并提出了有关过压保护的建议。