This paper analyzes lightning overvoltage spikes in an internal network of a large power plant. The cases considered are direct stroke to the phase conductor of the connected power transmission line and back flashover resulting from the lightning stroke to the transmission tower or shield wire. To investigate the transmitted overvoltages through transformers, high frequency models of the transformers are used. The voltage rise at the secondary side of each connected transformer at different voltage levels in the house load network of the power generation plant is analyzed. Protective measures are compared in order the study how to mitigate the transferred overvoltage at the different house load power system levels and to ensure that the impulse voltage is within the basic insulation level (BIL) of the connected equipment. Simulations using different combinations of protective surge arrestors and protective capacitors are done and recommendations on overvoltage protection are presented.
机译:本文分析了大型电厂内部网络中的闪电过压尖峰。所考虑的情况是直接行程到所连接的电力传输线的相导体和由雷击冲程到传输塔或屏蔽线产生的后闪络。为了通过变压器研究传输的过电压,使用变压器的高频模型。分析了在发电厂的房屋负载网络的不同电压电平下的每个连接变压器的次级侧的电压上升。比较保护措施,以便研究如何减轻不同房屋负载电力系统水平的转移过电压,并确保脉冲电压在连接设备的基本绝缘水平(BIL)内。采用不同组合的保护浪涌器和保护电容器的模拟,并提出了关于过电压保护的建议。