Data Center Temperature Control using PI System and MATLAB

机译:使用PI System和MATLAB的数据中心温度控制

获取原文

摘要

Several existing models are highly effective in predicting air temperature distributions of data centers. However, the complexity of these approaches requires significant computation time, making it difficult to control parameters in real time. Furthermore, lack of communication between inputs such as cooling infrastructure and outputs results in latency in receiving the relevant data and enacting changes. The goal of this case study is to demonstrate a simple heuristic model that enacts automatic controls to maintain a target server inlet air temperature by changing CRAC return air temperature set points. Data are collected and gathered with the PI System from OSIsoft, and are then imported into MATLAB, where regressions and conditionals are applied to generate a new optimal return air temperature set point. The new set point is written back into the PI system, which results in overwriting of the Building Management System via MODBUS communication. In addition, displays and notifications allow users for more effective monitoring of the conditions of the data center. The model developed from this case study represents an effective baseline for maintaining a target inlet air temperature for a server rack using real-time control techniques.
机译:现有的几种模型在预测数据中心的气温分布方面非常有效。但是,这些方法的复杂性需要大量的计算时间,从而难以实时控制参数。此外,冷却基础设施等输入与输出之间缺乏通信,导致接收相关数据和执行更改时出现延迟。本案例研究的目的是演示一个简单的启发式模型,该模型可通过更改CRAC回流空气温度设定点来实施自动控制,以维持目标服务器进气温度。使用OSIsoft的PI System收集和收集数据,然后将其导入MATLAB,在其中应用回归和条件生成新的最佳回风温度设定点。新的设定点被写回到PI系统中,从而导致通过MODBUS通讯覆盖楼宇管理系统。此外,显示和通知使用户可以更有效地监视数据中心的状况。通过本案例研究开发的模型代表了使用实时控制技术维持服务器机架目标进气温度的有效基准。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号