首页> 外文会议>Annual Conference for Protective Relay Engineers >Catching falling conductors in midair — detecting and tripping broken distribution circuit conductors at protection speeds
【24h】

Catching falling conductors in midair — detecting and tripping broken distribution circuit conductors at protection speeds

机译:在空中捕捉掉落的导线—以保护速度检测和跳闸损坏的配电线路导线

获取原文

摘要

When an overhead electric power distribution circuit conductor breaks-for example, when a car strikes a pole or a splice or clamp fails-the energized conductor falls to ground. The resulting high-impedance ground fault may be difficult or impossible to detect by relays located in the substation. In any case, no ground fault protection relay can operate until well after the time the fault has occurred-after the falling energized conductor has hit the ground and created a hazardous situation. For decades, utilities and equipment manufacturers have worked to develop methods for tripping these hazardous ground faults as quickly as possible. This paper describes a new falling conductor detection scheme that trips the affected circuit section in the narrow time window between the moment of the break and the time the conductor hits the ground. The affected circuit section is de-energized while the conductor is still falling, eliminating the risk of an arcing ground fault or energized circuits on the ground.
机译:当高架配电电路的导体断开时(例如,汽车撞到杆子或接头或夹钳失效),通电的导体会掉到地上。由此产生的高阻抗接地故障可能很难或无法通过位于变电站中的继电器检测到。在任何情况下,接地故障保护继电器都不能运行,直到故障发生之后很久之后-下降的带电导体触地并造成危险情况。几十年来,公用事业和设备制造商一直在努力开发出使这些危险的接地故障尽快跳闸的方法。本文介绍了一种新的跌落导体检测方案,该方案可在断裂时刻与导体触地之间的狭窄时间窗口内使受影响的电路部分跳闸。当导体仍在掉落时,受影响的电路部分将断电,从而消除了发生电弧接地故障或接地电路通电的风险。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号