首页> 外文会议>International Conference on Electrical Engineering and Informatics >Mitigating Spikes for EMC in Vibration Monitoring Systems of Generating Plant
【24h】

Mitigating Spikes for EMC in Vibration Monitoring Systems of Generating Plant

机译:在发电机振动监测系统中减轻EMC的尖峰

获取原文

摘要

Indonesia islands are situated in equatorial region with relative high density of thunderbolt rate. As developing country Indonesia builds many generating plants. During lightning stroke, some spikes occurred in turbine-generator vibration monitoring systems. Electromagnetic compatibility (EMC) problem was happened in the systems. This paper proposes mitigation technique to overcome spikes in vibration monitoring systems of a generating plant. The spikes displayed in the monitoring system were evaluated and will be mitigated. A filtering system is one of alternative solutions to cope this problem. Ferrite ring component which is a part of filtering system was recommended to put before load (the monitoring system). The result of Pspice simulation showed that the combination of ferrite ring and shunt capacitor to form L-C LPF can suppress the amplitude of the spikes effectively.
机译:印度尼西亚群岛位于赤道地区,具有相对高密度的雷霆率。随着发展中国家印度尼西亚建立了许多发电厂。在闪电行程中,一些尖峰发生在涡轮发电机振动监测系统中。系统中发生了电磁兼容性(EMC)问题。本文提出了缓解技术来克服发电厂振动监测系统的峰值。在监测系统中显示的尖峰进行了评估,并将被减轻。过滤系统是应对这个问题的替代解决方案之一。建议在负载(监控系统)之前将铁氧体环形组件置于过滤系统的一部分。 PSPICE仿真的结果表明,铁氧体环和并联电容器形成L-C LPF的组合可以有效地抑制尖峰的幅度。