The effect of the coaxial cable type and length on the lightning impulse parameters is often neglected. However, studies have shown that the coaxial cable length can affect the parameters that are calculated according to IEC 60060-1:2010. This study investigates how different coaxial cables influence the impulse waveforms by measuring the input and output of the cable under test with a 2-channel digitizer. Non-standard lightning impulses were generated using an impulse voltage calibrator. Results indicate that coaxial cables attenuate the test voltage and increase both the front time and time-to-half value.
机译:同轴电缆类型和长度对闪电脉冲参数的影响通常被忽略。然而,研究表明,同轴电缆长度可以影响根据IEC 60060-1:2010计算的参数。本研究调查了如何通过使用2通道数字转换器测量电缆的输入和输出来影响脉冲波形的不同同轴电缆。使用脉冲电压校准器产生非标准闪电脉冲。结果表明同轴电缆衰减测试电压并增加前时间和时间到半值。