首页> 外文期刊>Electrical Engineers, Proceedings of the Institution of >Impulse-strength measurements on compressed-gas insulation for extra-high-voltage power cables
【24h】

Impulse-strength measurements on compressed-gas insulation for extra-high-voltage power cables

机译:超高压电力电缆压缩气体绝缘的冲击强度测量

获取原文
获取原文并翻译 | 示例
           

摘要

Impulse-flashover measurements on a number of solid insulating materials in compressed-gas atmospheres at pressures up to 500 lbf/in2 are described. From the results of tests made with uniform-field and concentric-cylinder electrode systems, it is concluded that flashover occurs when the breakdown stress of the gas itself is reached at any point. The influence upon gas breakdown of placing thin coverings of solid insulating material in contact with metallic electrodes has also received attention. With a variety of coverings, improvements in impulse strength of approximately 50% were obtained with nitrogen and to a lesser, although still significant, extent with sulphur hexafluoride. The general levels of breakdown stress obtained are considered in relation to possible designs of extra-high-voltage power cables employing compressed gas as the major insulation.
机译:描述了在高达500 lbf / in2的压力下在压缩气体气氛中对多种固体绝缘材料的脉冲闪络测量。根据均匀场和同心圆柱电极系统的测试结果,可以得出结论,当气体本身在任何点达到击穿应​​力时,就会发生飞弧。将固体绝缘材料的薄覆盖物与金属电极接触放置对气体击穿的影响也受到关注。使用各种覆盖物,使用氮气可以将脉冲强度提高约50%,而使用六氟化硫可以将其提高到较小程度,尽管仍然很明显。与采用压缩气体作为主要绝缘材料的超高压电力电缆的可能设计有关,考虑了获得的一般击穿应力水平。