A case study on Power Quality issues in the Indian Railway traction sub-station

机译:印度铁路牵引变电站电能质量问题的案例研究

获取原文

摘要

The railway traction loads has more effect on power quality. Its effects on power quality cannot be ignored. The relevance of Power Quality (PQ) issue has recently augmented because of the increased use of power electronic equipments, which results in a voltage deviation and current waveforms. The performance and life expectancy of industrial electronics and electrical equipments is significantly affected by power supply anomalies caused by polluting loads at an industrial site and by utility normal operational activities. Hence railway traction loads have been taken as case study. Power quality issues have been studied by installing power quality monitoring system in traction sub-station1 and in traction sub-station2. In traction substation1, 2400 kVar rated capacitor alone is installed and where as in traction sub-station2, IGBT based DRPC (Dynamic Reactive Power Controller) with 1800 kVar is connected along with fixed 2400 kVar capacitor. The actual power quality issues of these traction sub stations were measured. The harmonics due to load currents, voltage and current unbalance measured are compared based on IEEE Standards 519-1992.
机译:铁路牵引负荷对电能质量的影响更大。它对电能质量的影响不容忽视。最近,由于越来越多地使用电力电子设备,导致电能质量(PQ)问题的相关性增加,从而导致电压偏差和电流波形。工业电子和电气设备的性能和预期寿命受到工业现场污染负荷和公用事业正常运行活动引起的电源异常的严重影响。因此,已将铁路牵引载荷作为案例研究。通过在牵引子站1和牵引子站2中安装电能质量监控系统,研究了电能质量问题。在牵引变电站1中,仅安装了2400 kVar额定电容器,而在牵引变电站2中,则安装了1800 kVar的基于IGBT的DRPC(动态无功功率控制器)和固定的2400 kVar电容器。测量了这些牵引变电站的实际电能质量问题。根据IEEE标准519-1992比较由负载电流,电压和电流不平衡引起的谐波。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号