Discharge Properties in Low Vacuum and Vacuum Monitoring Method for Vacuum Circuit Breakers

机译:真空断路器的低真空放电特性和真空监测方法

获取原文

摘要

One of the causes leading to the low performance of vacuum interrupters (VIs) is a slow leak. If no measures are taken, this phenomenon cannot be detected and the VI develops serious faults. Therefore, an effective monitoring technique is essential. We experimentally investigated the discharge properties in the low vacuum region of a VI. We measured the signal intensity of the discharge signal caused by the discharge occurring inside a model VI whose degree of vacuum could be varied. Pulse pattern and pulse waveforms were also measured in various pressures. To understand the pattern generating mechanism, we simulated these discharge patterns. Two noise reduction method using timer and frequency filter was examined. Finally, we introduce on-line vacuum-monitoring device with an alarm to warn of the deterioration of the vacuum degree of VIs.
机译:导致真空断电器低性能的原因之一(VIS)是缓慢的泄漏。如果没有采取措施,则无法检测到这种现象,VI产生严重的故障。因此,有效的监测技术至关重要。我们通过实验研究了VI的低真空区域中的放电特性。我们测量由在模型VI内发生的放电引起的放电信号的信号强度,其真空度可以改变。还在各种压力下测量脉冲图案和脉冲波形。为了理解模式生成机制,我们模拟了这些放电模式。检查了使用定时器和频率滤波器的两种降噪方法。最后,我们介绍了在线真空监测装置,警报警告导致Vis真空度的恶化。