Investigation and replacement of bus partial differential zones in a ring bus application at centerpoint energy

机译:中心点能量在环形公交车中的公交车局部差异区域的研究和更换

获取原文

摘要

This paper is based on the actual occurrence of the loss of service to all load at a CenterPoint Energy substation that serves three metropolitan underground 12.47 kV distribution networks. Subsequent investigation determined that the loss of service was caused by the maloperation of multiple, 69 kV bus electromechanical instantaneous overcurrent partial differential relay zones of protection for a fault in the 69 kV ring bus. Modeling and simulation substantiated that the maloperation occurred due to current transformer saturation in the presence of high DC offset current during a second unsuccessful automatic reclose attempt after all protection had operated properly for the initial fault and for the first unsuccessful automatic reclose attempt This event occurred in June of 2004 and a temporary fix was implemented shortly there after. Transient testing of the selected replacement protection system was conducted. The permanent solution is scheduled to be complete in early 2005.
机译:本文基于服务于三个城市地下12.47 kV配电网的CenterPoint能量变电站对所有负载的服务损失的实际发生。随后的调查确定,服务中断是由多个69 kV母线机电瞬时过电流部分差动继电保护区的误操作所引起的,该保护区为69 kV环形母线提供故障。建模和仿真证实,由于所有保护均已针对初始故障和首次未成功的自动重合闸进行了正确的保护,在第二次不成功的自动重合闸期间,由于存在高的直流偏置电流而导致电流互感器饱和,因此发生了误操作。 2004年6月,此后不久实施了临时修复。对选定的替换保护系统进行了瞬态测试。永久解决方案计划于2005年初完成。